日喀则Design and calculation of industrial coolers

日喀则

dustrial coolers,design

:本文围绕工业冷却器的设计与计算展开,阐述了工业冷却器在工业生产中的关键作用,其能有效地降低设备或工艺流程的温度,保障系统稳定运行,详细介绍了设计环节,包括依据不同的工业场景和冷却需求确定冷却器的类型,如风冷式、水冷式等,同时考虑冷却介质的特性、流量等参数,在计算方面,着重讲解了热负荷的计算方法,通过分析被冷却对象的热量产生速率、环境温度等因素,精准计算出所需的换热量,还涉及冷却器传热面积、传热系数等关键参数的计算,以确保冷却器能达到预期的冷却效果。

日喀则1、Design basis

日喀则

Design Standard for Steel Structures GB50017-2017Steel Structure Design Manual, China Construction Industry Press, January 2004

日喀则Code for Construction and Acceptance of Steel Structures (GB50205-2020)

日喀则

日喀则British Code for Design of Steel Structures (BS5950)

日喀则

日喀则2、Design load

日喀则

Load includes structural self weight, wind turbine constant load, live load, snow load, wind load, etc. The structural calculation adopts the ultimate stress method, therefore, the load value is larger than usual. The surface load is calculated based on the distribution coefficient and applied to the platform according to the line load. The wind load is calculated based on the wind vibration coefficient, body shape coefficient, and basic wind pressure to calculate the wind pressure values on four surfaces, which are then converted into line loads and applied to the columns. Auxiliary components such as stair handrails are applied to the stairs according to uniformly distributed loads.

日喀则1. Constant load

日喀则

The self weight of the steel structure is automatically calculated by the program, and the node weight is considered based on the self weight of the structure multiplied by 1.3. The weight and fluid load of the radiator are applied by external forces.

Platform constant load: 0.50kN/m2

2. Live load

日喀则

Live load of the platform for loading: 2.5kN/m2

日喀则

3. Snow load

日喀则According to relevant design data, the snow pressure can be basically calculated as 0.4N/m2.

日喀则

4. Wind load

日喀则

日喀则Calculate according to the maximum value.

日喀则

Basic wind pressure: 0.35kN/m2, height variation coefficient of 1.8, wind vibration coefficient: 1.5, ground roughness category: Class A

日喀则Class.

日喀则Is the standard value of wind load, is the wind vibration coefficient at height Z, is the shape coefficient of wind load, and is the coefficient of wind pressure height variation.

日喀则

日喀则When the standard value of wind load is less than 0.75kpa, calculate based on 0.75 kPa and multiply by 1.4 times the safety factor. Namely

日喀则

5. Temperature load

日喀则

日喀则The temperature difference is relatively small. The structural form is single, and the linear expansion of steel has a relatively small impact on the overall performance of the structure, which can be ignored.

日喀则

6 Earthquake loads

日喀则According to the seismic analysis design method: small earthquakes do not damage, medium earthquakes are repairable, and large earthquakes do not collapse. Small earthquake analysis can be divided into: bottom shear force method, response spectrum analysis, and elastic time history analysis. Medium earthquake analysis is calculated by multiplying small earthquake analysis by amplification factor.

Seismic fortification intensity: 8 degrees

日喀则

日喀则Design basic seismic acceleration peak value: 0.3g

日喀则

Construction site category: II site

日喀则

Design grouping: Second group

日喀则

Damping ratio: 0.05

日喀则This structure adopts MIADS software for overall modeling and analysis. During modeling, beam elements are mainly used for each structure. In order to facilitate loading, plate elements are established at the structural platform. Consolidation is used as the boundary condition at the bottom of each column, and constraints are applied at the connection between the column and the original structure according to the actual situation. The structure includes upright column, cross brace, slant support and upper and lower platform steel structure.

日喀则Load sub factors and load combinations:

日喀则Number

日喀则load

日喀则

日喀则Partial    coefficient remarks

日喀则

Partial    coefficient remarks

日喀则1

日喀则

日喀则dead load

日喀则1.3

2

日喀则Dead load, when   it has a restraining effect on uplift and   overturning

日喀则

1.0

日喀则3

日喀则

Dead load, when   acting together with wind load and live load

日喀则1.2

日喀则

4

日喀则

Live load

日喀则1.6

5

Live load, when   combined with wind load

1.2

日喀则

日喀则6

日喀则

Wind load

日喀则

日喀则1.4

日喀则

日喀则7

When combined   with wind load and live load

日喀则

日喀则1.2

日喀则

日喀则3、 Radiator calculation

日喀则

1. Material parameters

日喀则Aluminum alloy adopts 6005-T1, with tensile strength and yield strength equivalent to 6063-T5, tensile strength ≥ 150Mpa, yield stress ≥ 110 Mpa. According to the performance table of aluminum alloy, it is found that 6063-T5 has a tensile strength of 185Mpa, yield stress of 145 Mpa, and fatigue strength of 90MPa.

日喀则

日喀则2. Working condition analysis

日喀则The calculation of radiators can be divided into 1. lifting ondition,

日喀则

日喀则3. operating condition (operating condition is divided into

日喀则4.support and lifting point participate in force simultaneously.

日喀则5.support bears gravity, while lifting point bears horizontal force.

日喀则6.support does not bear any force, that is, when the overall structure is subjected to uneven settlement, there is a suspension at the bottom)

日喀则To ensure its stability, it is recommended that the foundation treatment should be pre compressed and settlement assessment should be carried out during the overall installation.

2.1 Hoisting conditions

At this point, the radiator is only considered for its own weight due to the lack of fluid injection, and is lifted and installed through a side lifting point. Because no other accessories were installed during modeling, in order to estimate the weight more accurately, its self weight coefficient was defined as 1.3.

日喀则

日喀则The radiator structure consists of 1, frame 2, support beam 3, heat exchange tube 4, tube plate, and other ancillary structures. As the heat exchange tube and support beam are fixed together through a corrugated plate, it can be considered that the heat exchange tube participates in the structural stress, which leads to strain and stress generation.

日喀则

日喀则The overall structural model is

Radiator structural model

The overall deformation of the radiator during the lifting process

日喀则

日喀则

日喀则

Stress cloud diagram of radiator during lifting process

日喀则

日喀则From its displacement cloud map, it can be seen that its overall deformation is 1.2mm, and the maximum stress is 15MPa

Stress cloud map of heat sink

日喀则

日喀则

 

日喀则

Displacement cloud map of heat sink

日喀则From its displacement cloud map, it can be seen that its overall deformation is 1mm and the maximum stress is 2MPa. Through calculation, it can be seen that horizontal lifting has little effect on the heat dissipation fins, and its deformation and stress are far less than the standard requirements.

日喀则

The vertical lifting situation is as follows:

日喀则

日喀则

日喀则Vertical lifting stress cloud map

日喀则

日喀则

日喀则

文章版权声明:除非注明,否则均为原创文章,转载或复制请以超链接形式并注明出处。

发表评论

快捷回复: 表情:
AddoilApplauseBadlaughBombCoffeeFabulousFacepalmFecesFrownHeyhaInsidiousKeepFightingNoProbPigHeadShockedSinistersmileSlapSocialSweatTolaughWatermelonWittyWowYeahYellowdog
评论列表 (暂无评论,14502人围观)

还没有评论,来说两句吧...

目录[+]

取消
微信二维码
微信二维码
支付宝二维码